The log interval was changed in B3 but did not change in the node

The commands from Boomerang to WIN gateway can only be sent after the WIN gateway first communicates with the Boomerang server. The commands to change anything in WIN gateway are placed in a queue in Boomerang waiting for the message from the gateway.

However, the WIN gateway doesn’t have a queue for commands it receives which means that it can only handle one at a time. A change in log interval can only be sent to the node next time it communicates with the gateway, so there may be some delay before its really set in the node. During this time, any new commands will be ignored by the gateway, so changing another MP’s logging interval may look ok in Boomerang, but it will never reach the node.

The only way around this is to manually check after a while that the node you’ve changed really has changed the log interval. If it hasn’t, change to a (preferably) shorter log interval, wait for the node to log at that interval and then change to the correct interval again and double check that it really transmits at that interval.