# SNTP server settings

**The WIN gateway MUST HAVE a correct date and time to operate.**&#x20;

The date and time are obtained from an SNTP server defined in [network-time-sntp-ntp-settings](https://help.boomerang3.com/win-gateway-installation-manual/gateway-configuration/network-time-sntp-ntp-settings "mention").

<figure><img src="https://2429681196-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2F0vLm0km8knyJJgcLOzxB%2Fuploads%2FHxd0cL8o8O41U9mnnqe6%2Fimage.png?alt=media&#x26;token=e50812af-72fc-43f2-a311-824814e2d3cd" alt="" width="563"><figcaption></figcaption></figure>

If there is no access to an SNTP server, the date shown after power on in Advanced -> Details will be 1970-01-01 and the gateway will not detect any linked or unlinked nodes.

SNTP server access is crucial and is a common cause of WIN gateway mulfunction when it sends no readings.