S2IOG2 accuracy
Type
Range
Accuracy
Remarks
Last updated
The analogue inputs have the following characteristics:
Voltage
0-10 V
0.5% of full scale
or better
Maximum input voltage: 12V
Input impedance: 250kΩ
Current
0-20 mA
0.5% of full scale
or better
Maximum input voltage: 4V
Input impedance: 200Ω±10%
Switch detection
N/A
N/A
Maximum input voltage: 12V
Minimum input impedance: 250kΩ
a
Last updated