S2IOG2 accuracy

The analogue inputs have the following characteristics:

Type
Range
Accuracy
Remarks

Voltage

0-10 V

0.5% of full scale

or better

Maximum input voltage: 12V

Input impedance: 250kΩ

Current

0-20 mA

0.5% of full scale

or better

Maximum input voltage: 4V

Input impedance: 200Ω±10%

Switch detection

N/A

N/A

Maximum input voltage: 12V

Minimum input impedance: 250kΩ

a

Last updated